The Pressure Reducing Valve shall be a diaphragm actuated, pilot controlled valve. The main valve body shall be ductile iron ASTM A 536. The stem of the basic valve shall be guided top and bottom. The diaphragm shall not be used as a seating sur- face. All internal and external ferrous surfaces shall be coated with a high quality, fusion epoxy coating. The pilot control shall be field adjustable from 15 psi to 150 psi. The valve shall be certified to NSF/ANSI Standard 61. The Pressure Reducing Valve with by-pass shall be a ZURN WILKINS Model ZW209BP
Compliance:
Features:
Keywords: Presure Reducing Valve, Low Flow Pressure Reducing, Pressure Regulator Valve, Zurn Pressure Regulator Valve, Zurn water Pressure Regulator Valve
Meets the requirements of NSF/ANSI 61*